Can an earth tag be used on an Exd cable gland entry?
Yes, providing it does not result in the length/number of threads being less than the standard requirements i.e. 5 full metric threads and 8mm of thread length. Refer to BS EN IEC 60079-14 2003. Also be aware of possible I.P. requirements.