Membership

Forgot your password?

For access to product selection applications, technical FAQ, downloads and more please register with us

S-Series Size 8 Enclosure

Technical Data

Increased Safety Exe. ex logo II 2 GD Exe II
Baseefa Certificate No. BAS01ATEX2106X.
Baseefa Certificate No. BAS01ATEX2105U.
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and test standards EN 50014, EN 50019 and EN 50281-1-1. IEC 60079-0 and IEC 60079-7.
IP66 ingress protection to IEC 60529 and EN 60529.
DTS01 deluge protection witnessed by EECS.
Operating temperature range -40°C to +80°C.
Temperature class and ambient T6 40°C.
Optional T5 with ambients up to 65°C.

Alternative certification options available:
flag of canada canadian standards association logo Exe II.
flag of U.S.A. underwriters laboratories logo AExe II/Exe II

S-Series Size 8 Enclosure

S-Series Size 8 enclosure dimensions

MAXIMUM QUANTITY OF ENTRIES PER FACE
(2 gland plates on faces B & D)
Thread Size M16 M20/O M20/A M25 M32 M40 M50 M63 M75
Bottom Face C
Quantity
64 # * 64 # * 42 30 18 13 8 6 4
Side Faces B & D
Quantity
128 # * 128 # * 84 60 36 26 16 12 8

# Serrated Washers/Locknuts with large outside diameters may foul on adjacent Cable Glands.
* Serrated Washers/Locknuts must not foul on aperture wall.

TERMINAL CAPACITY DATA
Terminal Type Conductor Size (mm²) Max.
Volts
Max. Physical
Terminal Content
Reduced Terminal Content
At Max. Terminal Amps
Min. Max. Terminal
Quantity
Amps Terminal
Quantity
Amps
WDU 2.5 0.5 2.5 550 852 3 17 21
WDU 4 0.5 4 750 720 4 16 28
WDU 6 0.5 6 550 540 5 14 36
WDU 10 1.5 10 550 438 8 12 50
WDU 16 1.5 16 550 360 11 11 66
WDU 35 2.5 35 750 270 20 9 109
WDU 70N 10 70 750 108 41 6 167
WDU 70/95 16 70 750 56 57 4 202
WDU 70/95 16 95 56 65 5
WDU 120/150 35 120 1100 46 78 5 234
WDU 120/150 150 46 85 6
WFF 35 2.5 35 1100 84 35 8 109
WFF 70 2.5 70 1100 46 66 7 167
WFF 120 6 120 1100 36 98 6 234
WFF 185 10 185 1100 13 197 5 307
WFF 300 25 300 1100 13 221 3 452

The Enclosure is supplied with an integral internal/external earth stud assembly.
WFF terminals are supplied fitted with cover.