Membership

Forgot your password?

For access to product selection applications, technical FAQ, downloads and more please register with us

S-Series Size 6 Enclosure

Technical Data

316 L Stainless Steel.
Increased Safety ex logo II 2 GD Exe II ExtD.
Size 6 (S6) Certificates:
Baseefa Certificate No. Baseefa08 ATEX 0208X
IECEx Certificate No. IECEx BAS 08.0065X
Z Size 6 (ZS6) Certificates:
Baseefa Certificate No. Baseefa08 ATEX 0207U
IECEx Certificate No. IECEx BAS 08.0064U
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and Test Standards: IEC/EN 60079-0, IEC/EN 60079-7, IEC/EN 61241-0 and IEC/EN 61241-1.
Ingress Protection: IP66 to IEC/EN 60529.
Deluge protection to DTS01.
Operating Temperature Range: -60°C to +80°C.
Temperature Class and Ambient: T6 40°C, optional T5 with ambients up to 65°C.

Alternative certification options available:
flag of canada canadian standards association logo Exe II.
flag of U.S.A. underwriters laboratories logo AExe II/Exe II.
flag of russia gost logo R-Exe IIU.
flag of kazakhstan Approved for use in Kazakhstan.

S-Series Size 6 Enclosure

S-Series Size 6 enclosure dimensions

MAXIMUM QUANTITY OF ENTRIES PER FACE
Thread Size M16 M20/O M20/A M25 M32 M40 M50 M63 M75
Bottom Face C
Quantity
44 # 42 32 26 14 11 6 4 3
Side Faces B & D
Quantity
56 # * 54 40 33 18 14 8 5 4
# Serrated washers/locknuts with large outside diameters may foul on adjacent cable glands.
* Serrated washers/locknuts must not foul on aperture wall.
TERMINAL CAPACITY DATA
Terminal Type Conductor Size (mm²) Max.
Volts
Max. Physical
Terminal Content
Reduced Terminal Content
At Max. Terminal Amps
Min. Max. Terminal
Quantity
Amps Terminal
Quantity
Amps
WDU 2.5 0.5 2.5 550 416 3 22 17
WDU 4 0.5 4 690 320 5 20 22
WDU 6 0.5 6 550 240 7 17 29
WDU 10 1.5 10 550 200 11 15 40
WDU 16 1.5 16 690 160 15 13 53
WDU 35 2.5 35 690 120 25 10 87
WDU 50 6 50 690 96 33 13 88
WDU 70N 10 70 690 50 54 9 134
WDU 70/95 16 70 690 19 86 8 134
WDU 70/95 16 95 690 19 97 11 134
WDU 120/150 35 120 690 16 114 9 162
WDU 120/150 35 150 690 16 120 10 162
WFF 35 2.5 35 1100 38 48 16 76
WFF 70 2.5 70 1100 16 100 13 116
WFF 120 6 120 1100 12 152 11 162
WFF 185 10 185 1100 9 212 7 234
WFF 300 25 300 1100 9 255 6 316

The enclosure is supplied with an integral internal/external earth stud assembly.
The terminals listed are restricted to a minimum operating temperature of -50°C.