Membership

Forgot your password?

For access to product selection applications, technical FAQ, downloads and more please register with us

S-Series Size 5 Enclosure

Technical Data

Increased Safety Exe. ex logo II 2 GD Exe II
Baseefa Certificate No. BAS01ATEX2106X.
Baseefa Certificate No. BAS01ATEX2105U.
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and test standards EN 50014, EN 50019 and EN 50281-1-1. IEC 60079-0 and IEC 60079-7.
IP66 ingress protection to IEC 60529 and EN 60529.
DTS01 deluge protection witnessed by EECS.
Operating temperature range -40°C to +80°C.
Temperature class and ambient T6 40°C.
Optional T5 with ambients up to 65°C.

Alternative certification options available:
flag of canada canadian standards association logo Exe II.
flag of U.S.A. underwriters laboratories logo AExe II/Exe II

S-Series Size 5 Enclosure

S-Series Size 5 enclosure dimensions

MAXIMUM QUANTITY OF ENTRIES PER FACE
Thread Size M16 M20/O M20/A M25 M32 M40 M50 M63 M75
Faces B, C & D
Quantity
40 # 40 # 24 20 10 8 # * 5 * 3 2

# Serrated Washers/Locknuts with large outside diameters may foul on adjacent Cable Glands.
* Serrated Washers/Locknuts must not foul on aperture wall.

TERMINAL CAPACITY DATA
Terminal Type Conductor Size (mm²) Max.
Volts
Max. Physical
Terminal Content
Reduced Terminal Content
At Max. Terminal Amps
Min. Max. Terminal
Quantity
Amps Terminal
Quantity
Amps
WDU 2.5 0.5 2.5 550 228 5 14 21
WDU 4 0.5 4 750 192 7 13 28
WDU 6 0.5 6 550 144 10 11 36
WDU 10 1.5 10 550 120 14 10 50
WDU 16 1.5 16 550 96 20 9 66
WDU 35 2.5 35 750 72 34 7 109
WDU 70N 10 70 750 40 60 5 167
WDU 70/95 16 70 750 15 96 3 202
WDU 70/95 16 95 15 107 4
WDU 120/150 35 120 1100 12 130 3 234
WDU 120/150 150 12 138 4
WFF 35 2.5 35 1100 15 75 7 109
WFF 70 2.5 70 1100 12 114 5 167
WFF 120 6 120 1100 9 173 4 234

The Enclosure is supplied with an integral internal/external earth stud assembly.
WFF terminals are supplied fitted with cover.