Membership

Forgot your password?

For access to product selection applications, technical FAQ, downloads and more please register with us

S-Series Size 4L Enclosure

Technical Data

316 L Stainless Steel.
Increased Safety ex logo II 2 GD Exe II ExtD.
Size 4L (S4L) Certificates:
Baseefa Certificate No. Baseefa08 ATEX 0208X
IECEx Certificate No. IECEx BAS 08.0065X
Z Size 4L (ZS4L) Certificates:
Baseefa Certificate No. Baseefa08 ATEX 0207U
IECEx Certificate No. IECEx BAS 08.0064U
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and Test Standards: IEC/EN 60079-0, IEC/EN 60079-7, IEC/EN 61241-0 and IEC/EN 61241-1.
Ingress Protection: IP66 to IEC/EN 60529.
Deluge protection to DTS01.
Operating Temperature Range: -60°C to +80°C.
Temperature Class and Ambient: T6 40°C, optional T5 with ambients up to 65°C.

Alternative certification options available:
flag of canada canadian standards association logo Exe II.
flag of U.S.A. underwriters laboratories logo AExe II/Exe II.
flag of russia gost logo R-Exe IIU.
flag of kazakhstan Approved for use in Kazakhstan.

S-Series Size 4 Enclosure

S-Series Size 4 enclosure dimensions

MAXIMUM QUANTITY OF ENTRIES PER FACE
Thread Size M16 M20/O M20/A M25 M32 M40 M50 M63 M75
Bottom Face C Quantity 44 # 42 32 26 14 11 6 4 3
Side Faces B & D
Quantity
26 # 18 18 11 6 5 4 * 2 1
# Serrated washers/locknuts with large outside diameters may foul on adjacent cable glands.
* Serrated washers/locknuts must not foul on aperture wall.
TERMINAL CAPACITY DATA
Terminal Type Conductor Size (mm²) Max.
Volts
Max. Physical
Terminal Content
Reduced Terminal Content
At Max. Terminal Amps
Min. Max. Terminal
Quantity
Amps Terminal
Quantity
Amps
WDU 2.5 0.5 2.5 550 252 4 19 17
WDU 4 0.5 4 690 188 6 18 22
WDU 6 0.5 6 550 144 9 15 29
WDU 10 1.5 10 550 112 13 13 40
WDU 16 1.5 16 690 96 18 11 53
WDU 35 2.5 35 690 72 30 8 87
WDU 50 6 50 690 60 39 11 88
WDU 70N 10 70 690 45 52 7 134
WDU 70/95 16 70 690 11 100 6 134
WDU 70/95 16 95 690 11 116 8 134
WDU 120/150 35 120 690 9 139 6 162
WDU 120/150 35 150 690 9 148 78 153
WFF 35 2.5 35 1100 22 58 113 76
WFF 70 2.5 70 1100 9 116 9 116
WFF 120 6 120 1100 7 163 7 162

The enclosure is supplied with an integral internal/external earth stud assembly.
The terminals listed are restricted to a minimum operating temperature of -50°C.