S-Series Size 4 Enclosure

Technical Data

Increased Safety Exe. ex logo II 2 GD Exe II ExtD A21
Baseefa Certificate No. Baseefa08 ATEX 0208X
Baseefa Certificate No. Baseefa08 ATEX 0207U
IECEx Certificate No. IECEx BAS 08.0065X
IECEx Certificate No. IECEx BAS 08.0064U
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and test standards IEC/EN 60079-0 and IEC/EN 60079-7, IEC/EN 61241-0 and IEC/EN 61241-1.
IP66 ingress protection to IEC/EN 60529.
DTS01 deluge protection witnessed by EECS.
Operating temperature range -60°C to +80°C.
Temperature class and ambient T6 40°C.
Optional T5 with ambients up to 65°C.
210mm deep option available.

Alternative certification options available:
flag of canada canadian standards association logo Exe II.
flag of U.S.A. underwriters laboratories logo AExe II/Exe II.
flag of russia gost logo R-Exe IIU.

S-Series Size 4 Enclosure

S-Series Size 4 enclosure dimensions

MAXIMUM QUANTITY OF ENTRIES PER FACE
Thread Size M16 M20/O M20/A M25 M32 M40 M50
Faces B, C & D
Quantity
26 # 26 # 18 9 6 4 4 *

# Serrated Washers/Locknuts with large outside diameters may foul on adjacent Cable Glands.
* Serrated Washers/Locknuts must not foul on aperture wall.

TERMINAL CAPACITY DATA
Terminal Type Conductor Size (mm²) Max.
Volts
Max. Physical
Terminal Content
Reduced Terminal Content
At Max. Terminal Amps
Min. Max. Terminal
Quantity
Amps Terminal
Quantity
Amps
WDU 2.5 0.5 2.5 550 168 6 22 17
WDU 4 0.5 4 690 141 8 20 22
WDU 6 0.5 6 550 108 11 17 29
WDU 10 1.5 10 550 84 16 14 40
WDU 16 1.5 16 690 72 22 13 53
WDU 35 2.5 35 690 54 36 9 87
WDU 70N 10 70 690 30 67 7 134
WDU 70/95 16 70 690 11 94 6 134
WDU 70/95 16 95 11 104 8
WDU 120/150 35 120 690 9 144 7 162
WDU 120/150 150 9 153 7
WFF 35 2.5 35 1100 11 76 11 76
WFF 70 2.5 70 1100 9 116 9 116
WFF 120 6 120 1100 7 162 7 162

The Enclosure is supplied with an integral internal/external earth stud assembly.
WFF terminals are supplied fitted with cover.