S-Series Size 4 Enclosure

Technical Data

Increased Safety Exe. ex logo II 2 GD Exe II
Baseefa Certificate No. BAS01ATEX2106X.
Baseefa Certificate No. BAS01ATEX2105U.
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and test standards EN 50014, EN 50019 and EN 50281-1-1. IEC 60079-0 and IEC 60079-7.
IP66 ingress protection to IEC 60529 and EN 60529.
DTS01 deluge protection witnessed by EECS.
Operating temperature range -40°C to +80°C.
Temperature class and ambient T6 40°C.
Optional T5 with ambients up to 65°C.
210mm deep option available.

Alternative certification options available:
flag of canada canadian standards association logo Exe II.
flag of U.S.A. underwriters laboratories logo AExe II/Exe II

S-Series Size 4 Enclosure

S-Series Size 4 enclosure dimensions

MAXIMUM QUANTITY OF ENTRIES PER FACE
Thread Size M16 M20/O M20/A M25 M32 M40 M50
Faces B, C & D
Quantity
26 # 26 # 18 9 6 4 4 *

# Serrated Washers/Locknuts with large outside diameters may foul on adjacent Cable Glands.
* Serrated Washers/Locknuts must not foul on aperture wall.

TERMINAL CAPACITY DATA
Terminal Type Conductor Size (mm²) Max.
Volts
Max. Physical
Terminal Content
Reduced Terminal Content
At Max. Terminal Amps
Min. Max. Terminal
Quantity
Amps Terminal
Quantity
Amps
WDU 2.5 0.5 2.5 550 168 6 15 21
WDU 4 0.5 4 750 141 8 13 28
WDU 6 0.5 6 550 108 12 12 36
WDU 10 1.5 10 550 84 17 10 50
WDU 16 1.5 16 550 72 24 9 66
WDU 35 2.5 35 750 54 40 7 109
WDU 70N 10 70 750 30 69 5 167
WDU 70/95 16 70 750 15 96 3 202
WDU 70/95 16 95 15 107 4
WDU 120/150 35 120 1100 9 149 3 234
WDU 120/150 150 9 158 4
WFF 35 2.5 35 1100 11 89 7 109
WFF 70 2.5 70 1100 9 134 5 167
WFF 120 6 120 1100 7 198 5 234

The Enclosure is supplied with an integral internal/external earth stud assembly.
WFF terminals are supplied fitted with cover.