S-Series Size 3 Enclosure

Technical Data

Increased Safety ex logo II 2 GD Exe II ExtD.
Size 3 (S3) Certificates:
Baseefa Certificate No. Baseefa08 ATEX 0208X
IECEx Certificate No. IECEx BAS 08.0065X
Z Size 3 (ZS3) Certificates:
Baseefa Certificate No. Baseefa08 ATEX 0207U
IECEx Certificate No. IECEx BAS 08.0064U
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and Test Standards: IEC/EN 60079-0, IEC/EN 60079-7, IEC/EN 61241-0 and IEC/EN 61241-1.
Ingress Protection: IP66 to IEC/EN 60529.
Deluge protection to DTS01.
Operating Temperature Range: -60°C to +80°C.
Temperature Class and Ambient: T6 40°C, optional T5 with ambients up to 65°C.
210mm deep option available.

Alternative certification options available:
flag of canada canadian standards association logo Exe II.
flag of U.S.A. underwriters laboratories logo AExe II/Exe II.
flag of russia gost logo R-Exe IIU.
flag of kazakhstan Approved for use in Kazakhstan.

S-Series Size 3 Enclosure

S-Series Size 3 enclosure dimensions

MAXIMUM QUANTITY OF ENTRIES PER FACE
Thread Size M16 M20/O M20/A M25 M32 M40 M50
Bottom Face C
Quantity
17 # 12 12 7 4 3 2
Side Faces B & D
Quantity
23 # 16 16 9 5 4 3
# Serrated washers/locknuts with large outside diameters may foul on adjacent cable glands.
TERMINAL CAPACITY DATA
Terminal Type Conductor Size (mm²) Max.
Volts
Max. Physical
Terminal Content
Reduced Terminal Content
At Max. Terminal Amps
Min. Max. Terminal
Quantity
Amps Terminal
Quantity
Amps
WDU 2.5 0.5 2.5 550 126 6 19 17
WDU 4 0.5 4 690 94 9 17 22
WDU 6 0.5 6 550 72 13 15 29
WDU 10 1.5 10 550 56 19 12 40
WDU 16 1.5 16 690 48 25 11 53
WDU 35 2.5 35 690 36 41 8 87
WDU 50N 6 50 690 28 56 11 88
WDU 70N 10 70 690 14 90 6 134
WFF 35 2.5 35 1100 11 76 11 76

The enclosure is supplied with an integral internal/external earth stud assembly.