S-Series Size 1 Enclosure

Technical Data

Increased Safety Exe. ex logo II 2 GD Exe II
Baseefa Certificate No. BAS01ATEX2106X.
Baseefa Certificate No. BAS01ATEX2105U.
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and test standards EN 50014, EN 50019 and EN 50281-1-1. IEC 60079-0 and IEC 60079-7.
IP66 ingress protection to IEC 60529 and EN 60529.
DTS01 deluge protection witnessed by EECS.
Operating temperature range -40°C to +80°C.
Temperature class and ambient T6 40°C.
Optional T5 with ambients up to 65°C.
210mm deep option available.

Alternative certification options available:
flag of canada canadian standards association logo Exe II.
flag of U.S.A. underwriters laboratories logo AExe II/Exe II

S-Series Size 1 Enclosure

S-Series size 1 enclosure dimensions

MAXIMUM QUANTITY OF ENTRIES
Thread Size M16 M20/O M20/A M25 M32
Quantity 5 # * 5 # * 3 2 1

# Serrated Washers/Locknuts with large outside diameters may foul on adjacent Cable Glands.
* Serrated Washers/Locknuts must not foul on aperture wall.

TERMINAL CAPACITY DATA
Terminal Type Conductor Size (mm²) Max.
Volts
Max. Physical
Terminal Content
Reduced Terminal Content
At Max. Terminal Amps
Min. Max. Terminal
Quantity
Amps Terminal
Quantity
Amps
WDU 2.5 0.5 2.5 550 30 13 12 21
WDU 4 0.5 4 750 25 18 11 28
WDU 6 0.5 6 550 19 26 10 36
WDU 10 1.5 10 550 15 38 8 50
WDU 16 1.5 16 550 13 51 7 66
WDU 35 2.5 35 750 9 90 6 109

The Enclosure is supplied with an integral internal/external earth stud assembly.