Membership

Forgot your password?

For access to product selection applications, technical FAQ, downloads and more please register with us

S-Series Size 1 Enclosure

Technical Data

316 L Stainless Steel.
Increased Safety ex logo II 2 GD Exe II ExtD.
Size 1 (S1) Certificates:
Baseefa Certificate No. Baseefa08 ATEX 0208X
IECEx Certificate No. IECEx BAS 08.0065X
Z Size 1 (ZS1) Certificates:
Baseefa Certificate No. Baseefa08 ATEX 0207U
IECEx Certificate No. IECEx BAS 08.0064U
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and Test Standards: IEC/EN 60079-0, IEC/EN 60079-7, IEC/EN 61241-0 and IEC/EN 61241-1.
Ingress Protection: IP66 to IEC/EN 60529.
Deluge protection to DTS01.
Operating Temperature Range: -60°C to +80°C.
Temperature Class and Ambient: T6 40°C, optional T5 with ambients up to 65°C.
210mm deep option available.

Alternative certification options available:
flag of canada canadian standards association logo Exe II.
flag of U.S.A. underwriters laboratories logo AExe II/Exe II.
flag of russia gost logo R-Exe IIU.
flag of kazakhstan Approved for use in Kazakhstan.

S-Series Size 1 Enclosure

S-Series size 1 enclosure dimensions

MAXIMUM QUANTITY OF ENTRIES PER FACE
Thread Size M16 M20/O M20/A M25 M32
Quantity 5 # * 4 3 2 1
# Serrated washers/locknuts with large outside diameters may foul on adjacent cable glands.
* Serrated washers/locknuts must not foul on aperture wall.
TERMINAL CAPACITY DATA
Terminal Type Conductor Size (mm²) Max.
Volts
Max. Physical
Terminal Content
Reduced Terminal Content
At Max. Terminal Amps
Min. Max. Terminal
Quantity
Amps Terminal
Quantity
Amps
WDU 2.5 0.5 2.5 550 30 13 18 17
WDU 4 0.5 4 690 25 17 16 22
WDU 6 0.5 6 550 19 24 13 29
WDU 10 1.5 10 550 15 34 11 40
WDU 16 1.5 16 690 13 45 9 53
WDU 35 2.5 35 690 9 75 6 87

The enclosure is supplied with an integral internal/external earth stud assembly.
The terminals listed are restricted to a minimum operating temperature of -50°C.