PL712 Enclosure

Technical Data

Increased Safety Exe. ex logo II 2 GD Exe IIC, Gb, IIIC, Db
Baseefa Certificate No. Baseefa08ATEX0272X.
Baseefa Certificate No. Baseefa08ATEX0271U.
IECEx Certificate No. IECEx BAS 08.0091X.
IECEx Certificate No. IECEx BAS 08.0090U.
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and test standards IEC/EN 60079-0, IEC/EN 60079-7, IEC/EN 61241-0 and IEC/EN 61241-1.
IP66 ingress protection to IEC 60529 and EN 60529.
IP66 ingress protection to IEC 60529 and EN 60529.
DTS01 deluge protection witnessed by EECS.
Operating temperature range -60°C to +75°C.
Temperature class and ambient T6 40°C.
Optional T5 with ambients up to 65°C.

Alternative certification options available:
flag of canada canadian standards association logo Exe II.
flag of U.S.A. underwriters laboratories logo AExe II/Exe II
flag of russia GOST logo GOST R-Exe IIU.

PL712 Enclosure

PL712 enclosure dimensions

MAXIMUM QUANTITY OF ENTRIES PER FACE
Thread Size M16/M20 M25
Quantity 2 1
TERMINAL CAPACITY DATA
Terminal Type Conductor Size (mm²) Max.
Volts
Max. Physical
Terminal Content
Reduced Terminal Content
At Max. Terminal Amps
Min. Max. Terminal
Quantity
Amps Terminal
Quantity
Amps
WDU 2.5N 0.5 2.5 420 12 14 8 17
WDU 2.5 0.5 2.5 550 10 15 8 17
WDU 4 0.5 4 690 10 18 7 22
WDU 6 0.5 6 550 7 25 5 29
WDU 10 1.5 10 550 6 34 4 40
BK6 1 4 275 1 20 N/A N/A
MK6/6 1 6 420 1 26 N/A N/A
HTB6 0.5 Max. Per
Pillar
550 1 Conductor
Size mm2
Max. Amps
Per Pillar
N/A N/A
2 x 10mm²
3 x 6mm²
4 x 4mm²
4 x 0.5mm² Min.
0.5
0.75
1
1.5
2.5
4
6
10
1
1
8
10
15
21
26
37

An earth terminal equal to that of the largest power terminal will be fitted.
The terminals listed are restricted to a minimum operating temperature of -50°C.