Membership

Forgot your password?

For access to product selection applications, technical FAQ, downloads and more please register with us

PL630 Enclosure

Technical Data

Increased Safety ex logo II 2 GD Exe II ExtD.
PL630 Certificates:
Baseefa Certificate No. Baseefa06ATEX0117X.
IECEx Certificate No. IECEx BAS 06.0028X.
ZPL630 Certificates:
Baseefa Certificate No. Baseefa06ATEX0116U.
IECEx Certificate No. IECEx BAS 06.0027U.
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and Test Standards: IEC/EN 60079-0, IEC/EN 60079-7, IEC/EN 61241-0 and IEC/EN 61241-1.
Ingress Protection: IP66 and IP67 to IEC/EN 60529.
Deluge protection to DTS01.
Operating Temperature Range: -60°C to +75°C.
°C, optional T5 with ambients up to 65°C.

Alternative certification options available:
flag of canada canadian standards association logo Exe II.
flag of U.S.A. underwriters laboratories logo AExe II/Exe II.
flag of russia gost logo R-Exe IIU.
flag of kazakhstan Approved for use in Kazakhstan.

PL630 Enclosure

PL630 enclosure dimensions

MAXIMUM QUANTITY OF ENTRIES PER FACE
Thread Size M16/M20 M25 M32 M40 M50 M63 M75
Quantity 10 8 3 3 2 2# 1#
# Not possible with an earth continuity plate.

Optional: Earth continuity plate.

TERMINAL CAPACITY DATA
Terminal Type Conductor Size (mm²) Max.
Volts
Max. Physical
Terminal Content
Reduced Terminal Content
At Max. Terminal Amps
Min. Max. Terminal
Quantity
Amps Terminal
Quantity
Amps
WDU 2.5 0.5 2.5 550 76 9 23 17
WDU 4 0.5 4 690 64 12 21 22
WDU 6 0.5 6 550 48 17 17 29
WDU 10 1.5 10 550 36 25 14 40
WDU 16 1.5 16 690 30 34 12 53
WDU 35 2.5 35 690 22 55 9 87
WDU 50N 6 50 690 11 88 11 88
WDU 70N 10 70 690 11 108 7 134

An earth terminal equal to that of the largest power terminal will be fitted.
The terminals listed are restricted to a minimum operating temperature of -50°C.