PL630 Enclosure
Technical Data
Increased Safety Exe.
II 2 GD Exe II
Baseefa Certificate No. BAS01ATEX2107X.
Baseefa Certificate No. BAS01ATEX2101U.
The above certificates are still current, however they are to be superseded by:
Baseefa Certificate No. Baseefa06ATEX0117X.
Baseefa Certificate No. Baseefa06ATEX0116U.
IECEx Certificate No. IECEx BAS 06.0028X.
IECEx Certificate No. IECEx BAS 06.0027U.
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and test standards EN 50014, EN 50019 and EN 50281-1-1. IEC 60079-0 and IEC 60079-7.
IP66 and IP67 ingress protection to IEC 60529 and EN 60529.
DTS01 deluge protection witnessed by EECS.
Operating temperature range -60°C to +75°C.
Temperature class and ambient T6 40°C.
Optional T5 with ambients up to 65°C.
Alternative certification options available:
Exe II.
AExe II/Exe II
PL630 Enclosure

| MAXIMUM QUANTITY OF ENTRIES PER FACE | |||||||
|---|---|---|---|---|---|---|---|
| Thread Size | M16/M20 | M25 | M32 | M40 | M50 | M63 | M75 |
| Quantity | 10 | 8 | 3 | 3 | 2 | 2 | 1 |
| TERMINAL CAPACITY DATA | ||||||||
|---|---|---|---|---|---|---|---|---|
| Terminal Type | Conductor Size (mm²) | Max. Volts |
Max. Physical Terminal Content |
Reduced Terminal Content At Max. Terminal Amps |
||||
| Min. | Max. | Terminal Quantity |
Amps | Terminal Quantity |
Amps | |||
| WDU 2.5 | 0.5 | 2.5 | 550 | 76 | 9 | 16 | 21 | |
| WDU 4 | 0.5 | 4 | 750 | 64 | 13 | 14 | 28 | |
| WDU 6 | 0.5 | 6 | 550 | 48 | 18 | 13 | 36 | |
| WDU 10 | 1.5 | 10 | 550 | 36 | 27 | 11 | 50 | |
| WDU 16 | 1.5 | 16 | 550 | 30 | 38 | 10 | 66 | |
| WDU 35 | 2.5 | 35 | 750 | 22 | 65 | 7 | 109 | |
| WDU 70N | 10 | 70 | 750 | 11 | 113 | 5 | 167 | |
An earth terminal equal to that of the largest power terminal will be fitted.