Membership

Forgot your password?

For access to product selection applications, technical FAQ, downloads and more please register with us

PL630 Enclosure

Technical Data

Increased Safety Exe. ex logo II 2 GD Exe II, ExtD.
Baseefa Certificate No. Baseefa06ATEX0117X.
Baseefa Certificate No. Baseefa06ATEX0116U.
IECEx Certificate No. IECEx BAS 06.0028X.
IECEx Certificate No. IECEx BAS 06.0027U.
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and test standards IEC 60079-0, IEC 60079-7, IEC 61241-0 and IEC 61241-1.
EN 60079-0, EN 60079-7, EN61241-0 and EN 61241-1.
IP66 and IP67 ingress protection to IEC 60529 and EN 60529.
DTS01 deluge protection witnessed by EECS.
Operating temperature range -60°C to +75°C.
Temperature class and ambient T6 40°C.
Optional T5 with ambients up to 65°C.

Alternative certification options available:
flag of canada canadian standards association logo Exe II.
flag of U.S.A. underwriters laboratories logo AExe II/Exe II.
flag of russia gost logo R-Exe IIU.
flag of kazakhstan Approved for use in Kazakhstan.

PL630 Enclosure

PL630 enclosure dimensions

MAXIMUM QUANTITY OF ENTRIES PER FACE
Thread Size M16/M20 M25 M32 M40 M50 M63 M75
Quantity 10 8 3 3 2 2 1
TERMINAL CAPACITY DATA
Terminal Type Conductor Size (mm²) Max.
Volts
Max. Physical
Terminal Content
Reduced Terminal Content
At Max. Terminal Amps
Min. Max. Terminal
Quantity
Amps Terminal
Quantity
Amps
WDU 2.5 0.5 2.5 550 76 9 23 17
WDU 4 0.5 4 690 64 12 21 22
WDU 6 0.5 6 550 48 17 17 29
WDU 10 1.5 10 550 36 25 14 40
WDU 16 1.5 16 690 30 34 12 53
WDU 35 2.5 35 690 22 55 9 87
WDU 70N 10 70 690 11 108 7 134

An earth terminal equal to that of the largest power terminal will be fitted.
The terminals listed are restricted to a minimum operating temperature of -50°C.