PL615 Enclosure

Technical Data

Increased Safety Exe. ex logo II 2 GD Exe II
Baseefa Certificate No. BAS01ATEX2107X.
Baseefa Certificate No. BAS01ATEX2101U.
The above certificates are still current, however they are to be superseded by:
Baseefa Certificate No. Baseefa06ATEX0117X.
Baseefa Certificate No. Baseefa06ATEX0116U.
IECEx Certificate No. IECEx BAS 06.0028X.
IECEx Certificate No. IECEx BAS 06.0027U.
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and test standards EN 50014, EN 50019 and EN 50281-1-1. IEC 60079-0 and IEC 60079-7.
IP66 and IP67 ingress protection to IEC 60529 and EN 60529.
DTS01 deluge protection witnessed by EECS.
Operating temperature range -60°C to +75°C.
Temperature class and ambient T6 40°C.
Optional T5 with ambients up to 65°C.

Alternative certification options available:
flag of canada canadian standards association logo Exe II.
flag of U.S.A. underwriters laboratories logo AExe II/Exe II

PL615 Enclosure

PL615 enclosure dimensions

MAXIMUM QUANTITY OF ENTRIES PER FACE
Thread Size M16/M20 M25 M32
Quantity 2 2 1
TERMINAL CAPACITY DATA
Terminal Type Conductor Size (mm²) Max.
Volts
Max. Physical
Terminal Content
Reduced Terminal Content
At Max. Terminal Amps
Min. Max. Terminal
Quantity
Amps Terminal
Quantity
Amps
WDU 2.5 0.5 2.5 550 14 17 9 21
WDU 4 0.5 4 750 12 23 8 28
WDU 6 0.5 6 550 9 33 7 36
WDU 10 1.5 10 550 7 48 6 50
WDU 16 1.5 16 550 6 65 5 66
HTB6 0.5 Max. Per
Pillar
550 1 Conductor
Size mm2
Max. Amps
Per Pillar
N/A N/A
2 x 10mm²
3 x 6mm²
4 x 4mm²
4 x 0.5mm² Min.
0.5
0.75
1
1.5
2.5
4
6
10
1
1
8
10
15
21
26
37

An earth terminal equal to that of the largest power terminal will be fitted.