PL615 Enclosure

Technical Data

Increased Safety ex logo II 2 GD Exe II ExtD.
PL615 Certificates:
Baseefa Certificate No. Baseefa06ATEX0117X.
IECEx Certificate No. IECEx BAS 06.0028X.
ZPL615 Certificates:
Baseefa Certificate No. Baseefa06ATEX0116U.
IECEx Certificate No. IECEx BAS 06.0027U.
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and Test Standards: IEC/EN 60079-0, IEC/EN 60079-7, IEC/EN 61241-0 and IEC/EN 61241-1.
Ingress Protection: IP66 and IP67 to IEC/EN 60529.
Deluge Protection to DTS01.
Operating Temperature Range: -60°C to +75°C.
Temperature Class and Ambient: T6 40°C, optional T5 with ambients up to 65°C.

Alternative certification options available:
flag of canada canadian standards association logo Exe II.
flag of U.S.A. underwriters laboratories logo AExe II/Exe II.
flag of russia gost logo R-Exe IIU.
flag of kazakhstan Approved for use in Kazakhstan.

PL615 Enclosure

PL615 enclosure dimensions

MAXIMUM QUANTITY OF ENTRIES PER FACE
Thread Size M16/M20 M25 M32
Quantity 2 2 1

Optional: Earth continuity plate.

TERMINAL CAPACITY DATA
Terminal Type Conductor Size (mm²) Max.
Volts
Max. Physical
Terminal Content
Reduced Terminal Content
At Max. Terminal Amps
Min. Max. Terminal
Quantity
Amps Terminal
Quantity
Amps
WDU 2.5 0.5 2.5 550 14 16 13 17
WDU 4 0.5 4 690 12 21 11 22
WDU 6 0.5 6 550 9 29 9 29
WDU 10 1.5 10 550 7 40 7 40
WDU 16 1.5 16 690 6 53 6 53
HTB6 0.5 Max. Per
Pillar
550 1 Conductor
Size mm²
Max. Amps
Per Pillar
N/A N/A
2 x 10mm²
3 x 6mm²
4 x 4mm²
4 x 0.5mm² Min.
See certificate for more options.
0.5
0.75
1
1.5
2.5
4
6
10
1
1
8
10
15
21
26
37

An earth terminal equal to that of the largest power terminal will be fitted.
The terminals listed are restricted to a minimum operating temperature of -50°C.