Membership

Forgot your password?

For access to product selection applications, technical FAQ, downloads and more please register with us

The Dual ATEX/IECEx Approved PL612 Enclosure

Technical Data

Increased Safety ex logo II 2 GD Exe II ExtD.
PL612 Certificates:
Baseefa Certificate No. Baseefa06ATEX0117X.
IECEx Certificate No. IECEx BAS 06.0028X.
ZPL612 Certificates:
Baseefa Certificate No. Baseefa06ATEX0116U.
IECEx Certificate No. IECEx BAS 06.0027U.
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and Test Standards: IEC/EN 60079-0, IEC/EN 60079-7, IEC/EN 61241-0 and IEC/EN 61241-1.
Ingress Protection: IP66 and IP67 to IEC/EN 60529.
Deluge protection to DTS01.
Operating Temperature Range: -60°C to +75°C.
Temperature Class and Ambient: T6 40°C, optional T5 with ambients up to 65°C.
Assembly Instructions adobe pdf logo

Please Note:

Hawke still offer enclosures to customer specifications available from our Box Modifiers.

PL612 enclosure with terminals

Materials And Finishes

Glass Reinforced Polyester. Natural Black Finish.
Flame Retardant to IEC 92.1 Clause 2.38

General Information

Standard PL612 Enclosures are supplied complete with:
Steel Earth Continuity Plate.
1 x M20 offset tapped entry per face (entries not plugged).

Pl612 enclosure dimensions

TERMINAL DATA
Terminal
Manufacturer
Terminal
Type
Terminal
Quantity
Conductor Size (mm²) Max.
Volts
Max.
Amps
Min. Max.
Weidmuller WDU 2.5N 12
+ 1 Rail Earth
0.5 2.5 420 16
Weidmuller WDU 2.5 10
+ 1 Rail Earth
0.5 2.5 550 17

Note: Terminals listed are only suitable for a minimum operating temperature of -50°C.