EZE-62 Enclosure

Technical Data

Increased Safety Exe. ex logo II 2 GD Exe II
Baseefa Certificate No. Baseefa08ATEX0364X
Baseefa Certificate No. Baseefa08ATEX0363U
IECEx Certificate No. IECEx BAS08.0125X
IECEx Certificate No. IECEx BAS08.0124U
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and test standards IEC/EN 60079-0, IEC/EN 60079-7, IEC/EN 61241-0 and IEC/EN 61241-1.
IP66 ingress protection to IEC/EN 60529.
DTS01 deluge protection witnessed by Baseefa 2001.
Operating temperature range -40°C to +80°C.
Temperature class and ambient T6 40°C.
Optional T5 with ambients up to 65°C.

EZE-62 Enclosure

EZE-62 enclosure dimensions

MAXIMUM QUANTITY OF ENTRIES
Thread Size M16 M20/Os/O M20/A M25 M32 M40 M50
Bottom Face Quantity 60 60 42 (36*) 27 (24*) 18 12 6

* Recommended maximum for Cable Gland installation.

TERMINAL CAPACITY DATA
Terminal Type Conductor Size (mm²) Max.
Volts
Typical Terminal Arrangements
3 Vertical Rail
(Max. Physical)
3 Vertical Rail
(Max. Current)
4 Vertical Rail *
(Max. Physical)
5 Vertical Rail *
(Max. Physical)
Min. Max. Terminal
Quantity
Current
(Amps)
Terminal
Quantity #
Current
(Amps)
Terminal
Quantity
Current
(Amps)
Terminal
Quantity
Current
(Amps)
WDU 2.5N 0.5 2.5 420 114 6 19 17 152 6 190 5
WDU 2.5 0.5 2.5 550 114 6 19 17 152 6 190 5
WDU 4 0.5 4 690 96 9 17 22 128 8 160 7
WDU 6 0.5 6 550 72 13 14 29 96 13 120 10
WDU 10 1.5 10 550 57 19 12 40 - - - -
WDU 16 1.5 16 690 48 25 10 53 - - - -
WDU 35 2.5 35 690 36 42 8 87 - - - -
Information in the above table is based on the maximum conductor size permitted for the terminal.
If earth terminals are required, the quantity should be taken from the maximum physical terminal quantity.
* Special / modified rail support arrangement.
# At maximum current terminal quantity could fit on one rail standard arrangement, would distribute quantity across 3 rails.

Notes:

  1. A combination of different sized entries is possible, please contact Hawke for more information.
  2. The table above gives an indication of potential terminal arrangements. Please contact Hawke for information on other arrangements or empty Enclosures.
  3. A combination of different sized terminals is possible, please contact Hawke for more information.
  4. Other terminal types are available.