Membership

Forgot your password?

For access to product selection applications, technical FAQ, downloads and more please register with us

EZE-42 Enclosure

Technical Data

Increased Safety Exe. ex logo II 2 GD Exe II
Baseefa Certificate No. Baseefa04ATEX0171X.
Baseefa Certificate No. Baseefa04ATEX0170U.
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and test standards EN 50014, EN 50019 and EN 50281-1-1. IEC 60079-0 and IEC 60079-7.
IP66 ingress protection to IEC 60529 and EN 60529.
DTS01 deluge protection witnessed by Baseefa 2001.
Operating temperature range -40°C to +80°C.
Temperature class and ambient T6 40°C.
Optional T5 with ambients up to 65°C.

EZE-42 Enclosure

EZE-42 dimensions

MAXIMUM QUANTITY OF ENTRIES
Thread Size M16 M20/Os/O M20/A M25 M32 M40 M50
Bottom Face Quantity 40 40 28 (24*) 18 (16*) 12 8 4

* Recommended maximum for Cable Gland installation.

TERMINAL CAPACITY DATA
Terminal Type Conductor Size (mm²) Max.
Volts
Typical Terminal Arrangements
2 Vertical Rail
(Max. Physical)
2 Vertical Rail
(Max. Current)
3 Vertical Rail *
(Max. Physical)
Min. Max. Terminal
Quantity
Current
(Amps)
Terminal
Quantity #
Current
(Amps)
Terminal
Quantity
Current
(Amps)
WDU 2.5N 0.5 2.5 420 76 9 14 21 114 7
WDU 2.5 0.5 2.5 550 76 9 14 21 114 7
WDU 4 0.5 4 750 64 12 13 28 96 10
WDU 6 0.5 6 550 48 17 11 36 72 14
WDU 10 1.5 10 550 38 25 10 50 57 21
WDU 16 1.5 16 750 32 35 9 66 48 29
WDU 35 2.5 35 750 24 60 7 109 36 49
Information in the above table is based on the maximum conductor size permitted for the terminal.
If earth terminals are required, the quantity should be taken from the maximum physical terminal quantity.
* Special / modified rail support arrangement.
# At maximum current terminal quantity could fit on one rail standard arrangement, would distribute quantity across 2 rails.

Notes:

  1. A combination of different sized entries is possible, please contact Hawke for more information.
  2. The table above gives an indication of potential terminal arrangements. Please contact Hawke for information on other arrangements or empty Enclosures.
  3. A combination of different sized terminals is possible, please contact Hawke for more information.
  4. Other terminal types are available.