EJB Enclosures

Technical Data

316 L Stainless Steel.
Increased Safety ex logo II 2 GD Exe II C Gb Extb, III C Db.
EJB Certificates:
Baseefa Certificate No. Baseefa08ATEX0208X
IECEx Certificate No. IECEx BAS08.0065X
ZEJB Certificates:
Baseefa Certificate No. Baseefa08ATEX0207U
IECEx Certificate No. IECEx BAS08.0064U
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and Test Standards: IEC/EN 60079-0, IEC/EN 60079-7, IEC/EN 61241-0 and IEC/EN 61241-1.
Ingress Protection: IP66 to IEC/EN 60529.
Deluge protection to DTS01.
Operating Temperature Range -40°C to +80°C.
Temperature Class and Ambient: T6 40°C, optional T5 with ambients up to 65°C.

EJB Enclosures

EZE-22 enclosure dimensions

DIMENSIONS
Dimension Size (mm) Size (mm)
S 120.0 150.0
T 2.0 2.0
V 80.5 90.5
W 96.0 126.0
X 126.0 156.0
Y 96.0 126.0
Z 148.0 178.0
MAXIMUM QUANTITY OF ENTRIES PER FACE
Thread Size M16 M20 M25 M32 M40 M50
Box Type EJB1 EJB2 EJB1 EJB2 EJB1 EJB2 EJB1 EJB2 EJB1 EJB2 EJB1 EJB2
Face A / C 6 10 6 8 3 3 2 3 2 2 0 1
Face B 4 8 4 6 2 2 1 2 1 2 0 1
Face D 6 10 6 8 3 3 2 3 2 2 0 1
TERMINAL CAPACITY DATA
Terminal Type Conductor Size (mm²) Max.
Volts
Max. Physical Terminal Content Reduced Terminal Content At Max. Terminal Amps
Terminal Qty. Amps Terminal Qty. Amps
Min. Max. EJB1 EJB2 EJB1 EJB2 EJB1 EJB2 EJB1 EJB2
WDU 2.5N 0.5 2.5 420 12 18 15 13 9 11 17 17
WDU 2.5 0.5 2.5 550 12 18 15 13 9 11 17 17
WDU 4 0.5 4 690 10 15 20 18 8 10 22 22
WDU 6 0.5 6 550 7 11 28 24 6 8 29 29
WDU 10 1.5 10 550 6 9 38 34 5 6 40 40
WDU 16 1.5 16 550 - 7 - 47 - - - -
BK 6 1 4 275 1   21 - - - - -
MK 6/6 1 6 420 1   26 - - - - -
HTB 6 0.5 Max. Per Pillar 550 1 1 Conductor
Size mm²
Max. Amps
Per Pillar
Conductor
Size mm²
Max. Amps
Per Pillar
N/A 1    
2 x 10mm²
3 x 6mm¹
4 x 4mm²
4 x 0.5mm²(Min)
See certificate for more options.
0.5
0.75
1
1.5
2.5
4
6
10
1
1
8
10
15
21
26
37
0.5
0.75
1
1.5
2.5
4
6
10
1
1
8
10
15
21
26
37

The enclosure is supplied with an integral internal/external earth stud assembly.
The terminals listed are restricted to a minimum operating temperature of -50°C.