Enclosure Accessories
IES10 Internal/External Earth Stud
Technical Data
Increased Safety EExe.
II 2 GD EExe II
Baseefa Certificate No. BAS01ATEX2111U.
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and test standards EN 50014, EN 50019 and EN 50281-1-1. IEC 60079-0 and IEC 60079-7.
Meets IP66 and IP67 ingress protection to IEC 60529 and EN 60529 in PL6 Series Enclosures.
Meets IP66 ingress protection to IEC 60529 and EN 60529 in PL7 Series and S-Series Enclosures.
DTS01 deluge protection witnessed by EECS.
Operating temperature range -60°C to +200°C.
Suitable for T6 and T5 applications.
Suitable for conductors up to 16mm².


Breather Draining Device
Technical Data
Fits M20 or M25 entry position (M20 as standard).
ATEX component approved and listed on Hawke ATEX Exe Enclosures.
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Meets IP66 ingress protection to IEC 60529 and EN 60529.
Operating temperature range -50°C to +85°C .
Note:
The PL6 Series Enclosures are marked on the rating label ‘IP66’ and ‘IP67’ and -60°C to +40°C as standard. When a Breather/Drain is fitted the rating label shall be amended to read ‘IP66’ and -50°C to +40°C.
Approved Components Available From Hawke
Hawke HTB6
Terminal Block Type HTB6
Baseefa Certificate No. BAS01ATEX2275U.
Pillar Earth Terminal
Pillar Earth Terminal PET5
Baseefa Certificate No. BAS01ATEX2274U.