Membership

Forgot your password?

For access to product selection applications, technical FAQ, downloads and more please register with us

PowerEx Calculations

To select the shell size of the connector, it is essential that you calculate the dissipated wattage of the arrangement. This ensures that the arrangement does not exceed the maximum permitted temperature classification with regard to the upper ambient temperature for the area of installation. (please refer to table 1 below for the maximum allowable dissipated wattage per connector size).

TABLE 1
Connector Size Upper Ambient
Temperature of +40°C
Upper Ambient
Temperature of +50°C
Upper Ambient
Temperature of +65°C
Temperature Class Temperature Class Temperature Class
T6 T5 T6 T5 T6 T5
Ex32P 20.5W 27.5W 15.75W 26W 7.5W 15.75W
Ex40P 22.5W 30.5W 17.5W 28W 8.7W 17.5W
Ex50P 25.8W 35.3W 20W 32.25W 10W 20W
Ex63P 30.2W 41.5W 23.5W 37.7W 11.7W 23.5W
Ex75P 36.3W 49.5W 28.25W 45.25W 14W 28.25W
  Maximum allowable dissipated wattage
Other ambient temperature options can be extrapolated from
table 1 above, or contact Hawke International for more information.
TABLE 2
Contact Size Combined Cable And Contact Resistance (Ohms) Contact Current Rating
50mm² 514 190 amps
70mm² 387 240 amps
95mm² 283 290 amps
120mm² 239 340 amps
150mm² 202 385 amps
185mm² 170 440 amps
240mm² 144 520 amps
300mm² 82 590 amps
400mm² 67 670 amps
500mm² 54 720 amps
630mm² 45 780 amps

Dissipated Wattage Calculation

Equation definitions:

W = Dissipated wattage factor of the connector

N = The number of conductors to be terminated/number of contacts required. (Note: A contact comprises of a pin and socket).

I = The current requirement per contact. (Note: This must be equal to or less than the maximum current rating of the contact, as shown in table 2 above).

R = The combined cable and contact resistance (see table 2 above).

Values pertinent to these definitions must then be input into the relevant fields below to calculate the dissipated wattage (W) of your chosen arrangement:

1. W = N x I ² x R
N I R Dissipated Wattage
(Watts)
W

Note: The result must be lower than the maximum figure shown in table 1 above, for the appropriate temperature class and ambient temperature).

e.g. T6 40°C ambient application with 4 x 95mm² conductors running at 160 amps.
N = 4 contacts
I = 160 amps
R = 0.000283 ohms (95mm² combined cable and contact resistance)

Therefore W = 4 x 25600 x 0.000283 = 28.9 watts.
Therefore an Ex63P Connector should be specified for this application as the shell size can accommodate the required 4 x 95mm² pin / socket inserts (see insert selection table) and the resultant dissipated wattage (28.9 watts) is below the maximum permitted 30.2 watts (see table 1 above).

This equation can also be transposed to facilitate the calculation of the maximum number of conductors permitted in your selected connector (calculator 2 below ) and the maximum allowable current within the upper ambient temperature of your location (calculator 3 below).

2. number of conductors formula
W R I Maximum Number Of
Conductors
N
3. maximum current formula
W N R Current
(Amps)
I
Note: The result must not exceed the maximum current rating of the contacts (see table 2 above)

Note: Unless otherwise requested, connectors will be marked as T5 with an upper ambient temperature of +40°C.

Calculations Data Sheet adobe pdf logo