InstrumEx Connectors Technical Data

4 Way
Explosion Protection ex logo II 2 G Exde IIC ExtD T85°C A21 ATEX
Exde IIC ExtD T85°C A21 IECEx
Ambient Temperature - 40°C to + 60°C
Certification Baseefa 06 ATEX 0061X
IECEx BAS06. 0018X
Ratings 4 Way
Voltage AC 250V
Current AC EN 60947-4-3 10A (AC21)
Current AC EN 60947-4-1 10A (AC1)
Current AC EN 60947-4-1 1A (AC3)
Frequency 50/60 Hz
Power Factor 0.9
Voltage DC 60V
Current DC EN 60947-4-3 2.5A (DC21)
Current DC EN 60947-4-1 2.5A (DC1)
Current DC EN 60947-4-1 0.5A (DC3)
Fuse Rating 4 Way
10 amp without thermal protection
20A gL with thermal protection
Maximum No. of make & break operations (EN61984)
On load 150
Off load 500
IP Rating IP66, IP67 and DTS01 deluge protected.
Note: Caps to be fitted to maintain IP ratings when the connector halves are separated.
Storage Temperature -50°C to +70°C
8 Way
Explosion Protection ex logo II 2 G Exde IIC ExtD T85°C A21 ATEX
Exde IIC ExtD T85°C A21 IECEx
Ambient Temperature - 40°C to + 60°C
Certification Baseefa 06 ATEX 0061X
IECEx BAS06. 0018X
Ratings 8 Way
Voltage AC 60V
Current AC EN 60947-4-3 1A (AC21)
Current AC EN 60947-4-1 1A (AC1)
Current AC EN 60947-4-1 0.1A (AC3)
Frequency 50/60 Hz
Power Factor 0.9
Voltage DC 60V
Current DC EN 60947-4-3 0.5A (DC21)
Current DC EN 60947-4-1 0.5A (DC1)
Current DC EN 60947-4-1 0.1A (DC3)
Fuse Rating 8 Way
2 amp without thermal protection
5A gL with thermal protection
Maximum No. of make & break operations (EN61984)
On load 150
Off load 500
IP Rating IP66, IP67 and DTS01 deluge protected.
Note: Caps to be fitted to maintain IP ratings when the connector halves are separated.
Storage Temperature -50°C to +70°C

Technical Data Sheet adobe pdf logo