| TECHNICAL DATA 4 WAY |
| Explosion Protection |
II 2 G Exde IIC ExtD T85°C A21 ATEX |
| Exde IIC ExtD T85°C A21 IECEx |
| Ambient Temperature |
-40°C to +60°C |
| Certification |
Baseefa 06 ATEX 0061X |
| IECEx BAS06.0018X |
| Ratings 4 Way |
Voltage AC 250V |
| Current AC EN 60947-4-3 10A (AC21) |
| Current AC EN 60947-4-1 10A (AC1) |
| Current AC EN 60947-4-1 1A (AC3) |
| Frequency 50/60 Hz |
| Power Factor 0.9 |
| Voltage DC 60V |
| Current DC EN 60947-4-3 2.5A (DC21) |
| Current DC EN 60947-4-1 2.5A (DC1) |
| Current DC EN 60947-4-1 0.5A (DC3) |
| Fuse Rating 4 Way |
10 amp without thermal protection |
| 20A gL with thermal protection |
| Maximum No. of make & break operation (EN61984) |
On load 150 |
| Off load 500 |
| IP Rating |
IP66, IP67 and DTS01 deluge protected. Note: Caps to be fitted to maintain IP ratings when the connector halves are separated
|
| Storage Temperature |
-50°C to +70°C |
| TECHNICAL DATA 8 WAY |
| Explosion Protection |
II 2 G Exde IIC ExtD T85°C A21 ATEX |
| Exde IIC ExtD T85°C A21 IECEx |
| Ambient Temperature |
-40°C to +60°C |
| Certification |
Baseefa 06 ATEX 0061X |
| IECEx BAS06.0018X |
| Ratings 8 Way |
Voltage AC 60V |
| Current AC EN 60947-4-3 1A (AC21) |
| Current AC EN 60947-4-1 1A (AC1) |
| Current AC EN 60947-4-1 0.1A (AC3) |
| Frequency 50/60 Hz |
| Power Factor 0.9 |
| Voltage DC 60V |
| Current DC EN 60947-4-3 0.5A (DC21) |
| Current DC EN 60947-4-1 0.5A (DC1) |
| Current DC EN 60947-4-1 0.1A (DC3) |
| Fuse Rating 4 Way |
2 amp without thermal protection |
| 5A gL with thermal protection |
| Maximum No. of make & break operation (EN61984) |
On load 150 |
| Off load 500 |
| IP Rating |
IP66, IP67 and DTS01 deluge protected. Note: Caps to be fitted to maintain IP ratings when the connector halves are separated |
| Storage Temperature |
-50°C to +70°C |