Membership

Forgot your password?

For access to product selection applications, technical FAQ, downloads and more please register with us

ControlEx Calculations

To select the shell size of the connector, it is essential that you calculate the dissipated wattage of the arrangement. This ensures that the arrangement does not exceed the maximum permitted temperature classification with regard to the upper ambient temperature for the area of installation. (please refer to table 1 below for the maximum allowable dissipated wattage per connector size).

TABLE 1
Connector Size Upper Ambient
Temperature of +40°C
Upper Ambient
Temperature of +50°C
Upper Ambient
Temperature of +60°C
Temperature Class Temperature Class Temperature Class
T6 T5 T6 T5 T6 T5
Ex16 5W 7W 4W 6W 2.6W 4.6W
Ex25 8W 11W 6W 10W 4W 7W
Ex32 10.5W 14.5W 8W 12W 5.4W 9W
Ex40 12W 17W 9W 14W 5.9W 10.5W
Ex50 13W 20W 10W 17W 6.5W 12.5W
Ex63 17W 29W 13W 24W 8.5W 17W
  Maximum allowable dissipated wattage
Other ambient temperature options can be extrapolated from
table 1 above, or contact Hawke International for more information.
TABLE 2
Contact Size Combined Cable And Contact Resistance (Ohms) Contact
Current
Rating
Soldered Crimped
1.5mm² 0.0166Ω 0.0173Ω 10 amps
2.5mm² 0.0102Ω 0.0109Ω 17 amps
6mm² 0.0047Ω 0.0054Ω 30 amps
10mm² 0.0027Ω 0.0033Ω 78 amps
16mm² 0.0018Ω 0.0024Ω 78 amps
25mm² 0.0012Ω 0.0018Ω 125 amps
35mm² 0.0009Ω 0.0015Ω 125 amps

Dissipated Wattage Calculation

Equation definitions:

W = Dissipated wattage factor of the connector

N = The number of conductors to be terminated/number of contacts required. (Note: A contact comprises of a pin and socket).

I = The current requirement per contact. (Note: This must be equal to or less than the maximum current rating of the contact, as shown in table 2 above).

R = The combined cable and contact resistance (see table 2 above).

Values pertinent to these definitions must then be input into the relevant fields below to calculate the dissipated wattage (W) of your chosen arrangement:

1. W = N x I ² x R
N I R Dissipated Wattage
(Watts)
W

(Note: The results must be lower than the maximum figure shown in table 1 above, for the appropriate temperature class and ambient temperature).

e.g. T6 40°C ambient application with 9 x 1.5mm² conductors running at 7 amps.
N = 9 contacts
I = 7 amps
R = 0.0166 Ω (1.5mm² soldered combined cable and contact resistance)

Therefore W = 9 x 49 x 0.0166 = 7.32 watts.
Therefore an Ex25 Connector should be specified for this application as the shell size can accommodate the required 9 x 1.5mm² pin / socket inserts (see insert selection table) and the resultant dissipated wattage (7.32 watts) is below the maximum permitted 8 watts (see table 1 above).

This equation can also be transposed to facilitate the calculation of the maximum number of conductors permitted in your selected connector (calculator 2 below ) and the maximum allowable current within the upper ambient temperature of your location (calculator 3 below).

2. number of conductors formula
W R I Maximum Number Of
Conductors
N
3. maximum current formula
W N R Current
(Amps)
I
Note: The result must not exceed the maximum current rating of the contacts (see table 2 above)

Note: Unless otherwise requested, connectors will be marked as T5 with an upper ambient temperature of +40°C.

Calculations Data Sheet adobe pdf logo