ICG 623 Cable Gland
Application
Outdoor or Indoor use.
For use with non-armoured elastomer and plastic insulated cables.
For particular use with:-
a) Cables that are not effectively filled, compact and/or circular, have tape bedding or have hygroscopic fillers.
b) Cables that exhibit ‘cold flow’ characteristics.
c) Enclosures containing an ignition source in gas group IIC areas or containing an ignition source in a Zone 1 area and exceeding 2 litres in volume.
Features
Provides a barrier seal between the individual insulated cores within the cable and prevents entry of the products of an explosion into the cable.
Assembly of the Cable Gland compresses and distributes the compound evenly to effect a barrier seal at the point of entry into the enclosure.
The compound chamber may be separated from the cured compound to ensure that the chamber has been effectively filled. If required, external voids can be repaired.
Provides a cable retention seal onto the cables outer sheath.
Two part sealing compound and assembly instructions are supplied with the Cable Gland.
Materials & Finishes
The ICG 623 Cable Gland is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminum.
Brass NPT entries are nickel plated as standard.
Technical Data
Flameproof Exd and Increased Safety Exe.
II 2 GD
Baseefa Certificate No. Baseefa06ATEX0058X.
IECEx Certificate No. IECEx BAS 06.0015X.
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Suitable for use in Gas Groups IIA, IIB and IIC.
Construction and test standards EN 50014, EN 50018, EN 50019 and EN 50281-1-1. IEC 60079-0, IEC 60079-1 and IEC 60079-7.
IP66, IP67 and IP68 (30 metres for 7 days) ingress protection to IEC 60529 and EN 60529 and NEMA 4X.
DTS01 deluge protection certified by ITS.
Operating temperature range -60°C to +80°C as standard.
Alternative certification options available:
Option available, Exd IIC, Exe II. Certificate No. 1024328 (LR 78713-9).
Option available, BR-Exd IIC/Exe II. Certificate No. CEPEL-EX-064/2001X.
AUS-Exd IIC/Exe II. Certificate No. AUS 03, 4010X.
Marine Approval. Certificate No. 06-LD142850B-PDA.
Marine Approval. Certificate No.E-8003.
ICG 623 Cable Gland

| CABLE GLAND SELECTION TABLE | |||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Size Ref. |
Entry Thread Size |
Cable Acceptance Details | ‘G’ Compressed Length |
Hexagon Dimensions |
|||||||||
| Inner Sheath/ Cores |
‘B’ Outer Sheath | ||||||||||||
| Metric | NPT * |
‘D’ Max. Over Cores |
‘E’ Max. Inner Sheath |
Max. No. Of Cores |
Standard Seal | Alternative (S) Seal |
Across Flats |
Across Corners |
|||||
| Standard | Option | Min. | Max. | Min. | Max. | ||||||||
| Os | M20 | ½" | - | 8.0 | 8.0 | 6 | 3.0 | 8.0 | - | - | 57.5 | 24.0 | 27.7 |
| O | M20 | ½" | - | 8.9 | 10.0 | 6 | 7.5 | 11.9 | - | - | 57.5 | 24.0 | 27.7 |
| A | M20 | ¾" | ½" | 11.0 | 12.5 | 10 | 11.0 | 14.3 | 8.5 | 13.4 | 56.3 | 30.0 | 34.6 |
| B | M25 | 1" | ¾" | 16.2 | 18.4 | 21 | 13.0 | 20.2 | 9.5 | 15.4 | 58.9 | 36.0 | 41.6 |
| C | M32 | 1¼" | 1" | 21.9 | 24.7 | 42 | 19.0 | 26.5 | 15.5 | 21.2 | 61.7 | 46.0 | 53.1 |
| C2 | M40 | 1½" | 1¼" | 26.3 | 29.7 | 60 | 25.0 | 32.5 | 22.0 | 28.0 | 62.6 | 55.0 | 63.5 |
| D | M50 | 2" | 1½" | 37.1 | 41.7 | 80 | 31.5 | 44.4 | 27.5 | 34.8 | 72.8 | 65.0 | 75.1 |
| E | M63 | 2½" | 2" | 47.8 | 53.5 | 100 | 42.5 | 56.3 | 39.0 | 46.5 | 75.7 | 80.0 | 92.4 |
| F | M75 | 3" | 2½" | 59.0 | 66.2/65.3 † | 120 | 54.5 | 68.2 | 48.5 | 58.3 | 77.7 | 95.0 | 109.6 |
| † Smaller value is applicable when selecting the option NPT entry thread. All Metric entry threads are 1.5mm pitch medium fit. All dimensions in millimetres (except*). |
|||||||||||||
Cable Gland Ordering Examples
Type/Size/Thread
e.g. ICG 623/C/M32
ICG 623/C/1¼" NPT
Cable Gland with Alternative Seal (S)
e.g. ICG 623/C/M32/S