Membership

Forgot your password?

For access to product selection applications, technical FAQ, downloads and more please register with us

755 Cable Gland/Connector

Application

Outdoor or Indoor use.
For use with armoured jacketed cable, as permitted by the NEC.

Features

Provides a barrier seal between the individual insulated conductors within the cable and prevents entry of the products of an explosion into the cable.
Assembly of the Cable Gland/Connector compresses and distributes the compound evenly to create a barrier seal at the point of entry into the enclosure.
Provides an outer deluge seal to prevent moisture ingress to the cable armour and enclosure.
Deluge seal is colored red to indicate Hazardous Locations product.
Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer jacket.
Two part sealing compound and assembly instructions are supplied with the Cable Gland/Connector.

Materials & Finishes

The 755 Cable Gland/Connector is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminum.
Brass NPT entries are nickel plated as standard.

Technical Data

UL Listed for use in Class 1, Division 2, Gas Groups A, B , C and D.
UL Listed for use in Class 1, Zone 2, Gas Groups IIA, IIB and IIC.
UL Listed AExd IIC and AExe II Class 1, Zone 2.
Construction and test standards flag of U.S.A flag of canada underwriters laboratories logo UL Listed hazardous locations in USA and Canada. E84940. UL Certificate E84940.
ULc Certificate E84940.
IP66, IP67 and IP68 (30 metres for 7 days) ingress protection to IEC 60529, EN 60529 and NEMA 4X.
DTSO1 deluge tested by ITS.
Operating temperature range -50°C to +60°C as standard.
Alternative certification options available:
DNV logo Marine Approval. Certificate No. E-8003
ABS logo Marine Approval Certificate No. 06-LD142850D-PDA.


755 Cable Gland/Connector

755 cable gland
CABLE GLAND/CONNECTOR SELECTION TABLE
Size
Ref.
Entry
Thread Size
Cable Acceptance Details ‘G’
Compressed
Length
Hexagon
Dimensions
Inner Sheath/Cores ‘B’
Outer
Jacket
‘C’
NPT Metric
*
‘D’
Max.
Over
Cores
‘E’
Max.
Inner
Sheath
Max.
No.
Of
Cores
Across
Flats
Across
Corners
Standard Option Min. Max. Steel Wire
Armour
Braid Tape
Os ½" - M20 ‡ 0.35" 0.46" 6 0.22" 0.47" 0.036" / 0.049" 0.008" / 0.013" 0.008" / 0.031" 2.80"" 0.94" 1.09"
O ½" - M20 ‡ 0.35" 0.46" 6 0.37" 0.63" 0.036" / 0.049" 0.008" / 0.013" 0.008" / 0.031" 2.80" 0.94" 1.09"
A ½" ¾" M20 0.43" 0.49" 10 0.49" 0.81" 0.036" / 0.049" 0.008" / 0.013" 0.008" / 0.031" 2.83" 1.18" 1.36"
B ¾" 1" M25 0.64" 0.72" 21 0.66" 1.02" 0.049" / 0.062" 0.008" / 0.013" 0.008" / 0.039" 2.94" 1.42" 1.64"
C 1" 1¼" M32 0.86" 0.97" 42 0.87" 1.30" 0.062" / 0.078" 0.008" / 0.013" 0.008" / 0.055" 3.10" 1.81" 2.09"
C2 1¼" 1½" M40 1.04" 1.16" 60 1.10" 1.61" 0.062" / 0.078" 0.008" / 0.013" 0.008" / 0.070" 3.26" 2.16" 2.50"
D 2" 1½" M50 1.46" 1.64" 80 1.42" 2.07" 0.078" / 0.098" 0.008" / 0.013" 0.008" / 0.070" 3.35" 2.55" 2.96"
E 2½" 2" M63 1.88" 2.11" 100 1.81" 2.57" 0.098" 0.008" / 0.013" 0.008" / 0.070" 3.56" 3.14" 3.64"
F 3" 2½" M75 2.32" 2.61"/2.57" † 120 2.24" 3.07" 0.098" 0.008" / 0.013" 0.008" / 0.070" 3.76" 3.73" 4.31"
† Smaller value is applicable when selecting the standard NPT entry thread.
‡Sizes Os and O are available with an M16 thread size. For O size with M16 thread, the maximum cable inner sheath diameter is 0.43".
All metric entry threads are 1.5mm pitch medium fit.
All dimensions in inches (except*).

Cable Gland/Connector Ordering Examples

Type/Size/Thread
e.g. 755/C/1" NPT