711 Cable Gland/Connector
Application
Outdoor or Indoor use.
For use with continuous corrugated aluminum, Metal Clad (MCHL) cable.
Features
Provides 360° armor grounding which is fully inspectable.
Grounding device remains in contact with the cable when disassembled for inspection.
Provides a barrier seal between the individual insulated cores within the cable and prevents entry of the products of an explosion into the cable.
Assembly of the Cable Gland/Connector compresses and distributes the compound evenly to create a barrier seal at the point of entry into the enclosure.
Provides an outer deluge seal to prevent moisture ingress to the cable armour and enclosure.
Deluge seal is colored red to indicate Hazardous Locations product.
Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer jacket.
Two part sealing compound and assembly instructions are supplied with the Cable Gland/Connector.
Materials & Finishes
The 711 Cable Gland/Connector is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminum.
Brass NPT entries are nickel plated as standard.
Technical Data
UL Listed for use in Class 1, Division 1, Gas Groups A, B , C and D.
UL Listed for use in Class 1, Zone 1, Gas Groups IIA, IIB and IIC.
UL Listed AExd IIC and AExe II Class 1, Zone 1.
Construction and test standards
UL Listed hazardous locations in USA and Canada. E84940. UL Certificate E84940.
ULc Certificate E84940.
IP66, IP67 and IP68 (30 metres for 7 days) ingress protection to IEC 60529, EN 60529 and NEMA 4X.
DTSO1 deluge tested by ITS.
Operating temperature range -50°C to +60°C as standard.
Alternative certification options available:
Marine Approval. Certificate No. E-8003
Marine Approval. Certificate No. 06-LD142850D-PDA.
711 Cable Gland/Connector

| CABLE GLAND/CONNECTOR SELECTION TABLE | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Size Ref. |
Entry Thread Size |
Cable Acceptance Details | ‘G’ Compressed Length |
Hexagon Dimensions |
||||||||
| Inner Sheath/Cores | ‘B’ Outer Jacket |
|||||||||||
| NPT | Metric * |
‘D’ Max. Over Cores |
‘E’ Armour Sheath |
Max. No. Of Cores |
Across Flats |
Across Corners |
||||||
| Standard | Option | Min. | Max. | Min. | Max. | |||||||
| A | ½" | ¾" | M20 | 0.43" | 0.41" | 0.64" | 10 | 0.49" | 0.81" | 2.74" | 1.18" | 1.36" |
| B | ¾" | 1" | M25 | 0.64" | 0.49" | 0.93" | 21 | 0.66" | 1.02" | 2.95" | 1.42" | 1.64" |
| C | 1" | 1¼" | M32 | 0.86" | 0.85" | 1.23" | 42 | 0.87" | 1.30" | 3.04" | 1.81" | 2.09" |
| C2 | 1¼" | 1½" | M40 | 1.04" | 1.17" | 1.59" | 60 | 1.10" | 1.61" | 3.09" | 2.16" | 2.50" |
| D | 2" | 1½" | M50 | 1.46" | 1.37" | 1.96" | 80 | 1.42" | 2.07" | 3.37" | 2.55" | 2.96" |
| E | 2½" | 2" | M63 | 1.88" | 1.76" | 2.55" | 100 | 1.81" | 2.57" | 3.65" | 3.14" | 3.64" |
| F | 3" | 2½" | M75 | 2.32" | 2.29" | 2.98" | 120 | 2.24" | 3.07" | 3.73" | 3.73" | 4.31" |
| ‘H’ size cable gland/connector available. Contact Hawke International for details. | ||||||||||||
| H | 3½" | 3" | M90 | 2.79" | 2.93" | 3.47" | 120 | 3.07" | 3.52" | 4.33" | 4.18" | 4.84" |
| A - F size metric entry threads are 1.5mm pitch as standard with 15mm length of thread. For H size Cable Glands and above, a 2mm pitch is supplied as standard with a 20mm length of thread (1.5mm pitch with 15mm length of thread can be supplied) please specify when ordering. All dimensions in inches (except*). |
||||||||||||
Cable Gland/Connector Ordering Examples
Type/Size/Thread