501/423 Cable Gland
Application
The 501/423 cable gland provides two independent seals on non-armoured elastomer and plastic insulated cables. The first is a flameproof seal on the inner or outer cable sheath, with an additional IP seal on the outer sheath. The cable gland is dual certified Exd and Exe and is suitable for installation in Zone 1 (21) and Zone 2 (22) hazardous areas.
Features
Provides superior cable retention to standard unarmoured cable glands, with seal at two independent points.
When used in increased safety applications, this cable gland may be used with braided cable where the braid and the outer sheath pass into the enclosure. The braid must be suitably terminated inside the enclosure.
Manufactured in brass (standard), nickel plated brass, 316 stainless steel or aluminium.
Brass NPT entries are nickel plated as standard.
Technical Data
Flameproof Exd and Increased Safety Exe.
II 2 GD ExtD A21.
Baseefa Certificate No. Baseefa06ATEX0056X.
IECEx Certificate No. IECEx BAS 06.0013X.
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Suitable for use in Gas Groups IIA, IIB and IIC.
Construction and test standards IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 61241-0, IEC 61241-1.
IP66, IP67 and IP68 (30 metres for 7 days) ingress protection to IEC 60529, EN 60529 and NEMA 4X.
DTS01 deluge protection certified by ITS.
Additional deluge protection seal also available.
Operating temperature range -60°C to +100° as standard.
Alternative certification options available:
Option available, Exd IIC, Exe II. Certificate No. 1015065 (LR 78713-7).
Option available, BR-Exd IIC/Exe II. Certificate No. CEPEL-EX-060/2001X.
Option available, GOST R-Exd IICU/Exe IIU.
Option available, Exd IIC/Exe II/DIP A21 IP66.
Marine Approval. Certificate No. 06-LD142850A-PDA.
Marine Approval. Certificate No.E-8003.
501/423 Cable Gland

| CABLE GLAND SELECTION TABLE | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Size Ref. |
Entry Thread Size |
Thread Length ‘H’ |
Cable Acceptance Details | ‘G’ Compressed Length |
Hexagon Dimensions |
||||||
| Outer Sheath ‘B’ | |||||||||||
| Metric | NPT * |
Standard Seal |
Alternative (S) Seal |
Across Flats |
Across Corners |
||||||
| Standard | Option | Min. | Max. | Min. | Max. | ||||||
| Os | M20 ‡ | ½" | - | 15.0 | 3.0 | 8.0 | - | - | 40.0 | 24.0 | 27.7 |
| O | M20 ‡ | ½" | - | 15.0 | 7.5 | 11.9 | - | - | 40.0 | 24.0 | 27.7 |
| A | M20 | ¾" | ½" | 15.0 | 11.0 | 14.3 | 8.5 | 13.5 | 40.1 | 30.0 | 34.6 |
| B | M25 | 1" | ¾" | 15.0 | 13.0 | 20.2 | 9.5 | 15.4 | 44.3 | 36.0 | 41.6 |
| C | M32 | 1¼" | 1" | 15.0 | 19.0 | 26.5 | 15.5 | 21.2 | 47.2 | 46.0 | 53.1 |
| C2 | M40 | 1½" | 1¼" | 15.0 | 25.0 | 32.5 | 22.0 | 28.0 | 49.6 | 55.0 | 63.5 |
| D | M50 | 2" | 1½" | 15.0 | 31.5 | 44.4/42.3 † | 27.5 | 34.8 | 64.6 | 65.0 | 75.1 |
| E | M63 | 2½" | 2" | 15.0 | 42.5 | 56.3/54.3 † | 39.0 | 46.5 | 64.8 | 80.0 | 92.4 |
| F | M75 | 3" | 2½" | 15.0 | 54.5 | 68.2/65.3 † | 48.5 | 58.3 | 68.0 | 95.0 | 109.6 |
| G | M80 | 3½" | - | 20.0 | 67.0 | 73.0 | - | - | 68.0 | 106.4 | 123.0 |
| H | M90 | 3½" | - | 20.0 | 67.0 | 77.6 | - | - | 68.0 | 115.0 | 132.8 |
| J | M100 | 4" | - | 20.0 | 75.0 | 91.6 | - | - | 68.0 | 127.0 | 146.7 |
| † Smaller value is applicable when selecting reduced NPT entry option. ‡ Sizes Os and O are available with an M16 thread size. For O size with M16 thread, the maximum cable outer sheath diameter is 10.9 mm. Os - F size metric entry threads are 1.5mm pitch as standard. For G size Cable Glands and above, a 2mm pitch is supplied as standard (1.5mm pitch with 15mm length of thread can be supplied) please specify when ordering. All dimensions in millimetres (except * where dimensions are in inches). |
|||||||||||
Cable Gland Ordering Examples
Type/Size/Thread
e.g. 501/423/C/M32
501/423/C/1¼" NPT
Cable Gland with Alternative Seal (S)
e.g. 501/423/C/M32/S
501/423/C/1¼" NPT/S