151/RAC Cable Gland

Application

151/RAC cable glandOutdoor or indoor use.
For use with single wire armour ‘W’, wire braid ‘X’, aluminium strip armour 'Y' and steel tape armour ‘Z’ elastomer and plastic insulated cables.

Features

Provides armour clamping using one clamping arrangement for all armour/braid types.
Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer sheath.

Materials & Finishes

The 151/RAC cable gland is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium.
Brass NPT entries are nickel plated as standard.

Technical Data

Construction and test standards: EN 50262, BS 6121 : Part 1 Type CW, CX, CY and CZ.
Ingress Protection: IP66 to IEC/EN 60529.
Deluge protection to DTS01. (Deluge seal optional).
Operating Temperature Range: -60°C to +100°C.

151/RAC cable gland
CABLE GLAND SELECTION TABLE
Size
Ref.
Entry Thread
Size
‘H’
Thread
Length
Cable Acceptance Details ‘G’
Compressed
Length
Hexagon
Dimensions
‘A’
Inner Sheath
‘B’
Outer Sheath
‘C’
Armour/Braid
Metric NPT
*
Max. Min. Max. Orientation
1
Orientation
2
Across
Flats
Across
Corners
Standard Option
Os M20 ‡ ½" - 15 8.0 5.5 12.0 0.8 / 1.25 0 / 0.8 52.0 24.0 26.5
O M20 ‡ ½" - 15 11.9 9.5 16.0 0.8 / 1.25 0 / 0.8 52.0 24.0 26.5
A M20 ¾" ½" 15 14.3 12.5 20.5 0.8 / 1.25 0 / 0.8 53.0 30.0 32.5
B M25 1" ¾" 15 20.2 16.9 26.0 1.25 / 1.6 0 / 0.7 69.5 36.0 39.5
C M32 1¼" 1" 15 26.5 22.0 33.0 1.6 / 2.0 0 / 0.7 64.0 46.0 50.5
C2 M40 1½" 1¼" 15 32.5 28.0 41.0 1.6 / 2.0 0 / 0.7 68.3 55.0 60.6
D M50 2" 1½" 15 44.4/42.3 † 36.0 52.6 1.8 / 2.5 0 / 1.0 79.0 65.0 70.8
E M63 2½" 2" 15 56.3/54.3 † 46.0 65.3 1.8 / 2.5 0 / 1.0 78.9 80.0 88.0
F M75 3" 2½" 15 68.2/65.3 † 57.0 78.0 1.8 / 2.5 0 / 1.0 83.7 95.0 104.0
G M80 3½" - 20 72.0 75.0 89.5 2.0/3.5 0/1.0 95.6 106.4 115.0
H M90 3½" - 20 80.0 75.0 89.5 2.0/3.5 0/1.0 95.6 115.0 130.0
J M100 4" - 20 90.0 88.0 104.5 2.5/4.0 0/1.0 95.6 127.0 142.0
All dimensions in millimetres (except * where dimensions are in inches).
Os - F size metric entry threads are 1.5mm pitch as standard. For G size cable glands and above, a 2mm pitch is supplied as standard (1.5mm pitch with 15mm length of thread can be supplied) please specify when ordering.
† Smaller value is applicable when selecting reduced NPT entry option.
‡ Sizes Os and O are available with an M16 thread size. For O size with M16 thread, maximum cable inner sheath diameter is 10.9mm.

151/RAC Cable Gland

Alternative Reversible Armour Clamping Ring (RAC)

SELECTION TABLE
Size
Ref.
Steel Wire Armour/Braid/Tape
Orientation 1 Orientation 2
B 0.9 / 1.25 0.5 / 0.9
C 1.2 / 1.6 0.6 / 1.2
C2 1.2 / 1.6 0.6 / 1.2
D 1.45 / 1.8 1.0 / 1.45
E 1.45 / 1.8 1.0 / 1.45
F 1.45 / 1.8 1.0 / 1.45

Ordering Information

Cable Gland Type/Size/Thread
e.g. 151/RAC/C/M32
151/RAC/C/1¼" NPT

Ordering Information with Alternative Clamping Ring

Cable Gland Type/Size/Thread/AR
e.g. 151/RAC/C/M32/AR
151/RAC/C/1¼" NPT/AR